Technical data
136 •  BACnet/IP Controller 750-830 
 Fault behavior 
 WAGO-I/O-SYSTEM 750 
BACnet/IP Controller 
3.1.10.2  Internal Bus Error 
An internal bus failure occurs, for example, if a bus module is removed. If the 
error occurs during operation, the output modules operate as they do during an 
internal bus stop. 
The "I/O" LED flashes red. 
The controller generates an error message (error code and error argument). 
If the internal bus failure is resolved, the controller starts up after turning the 
power off and on again as for a normal startup. The process data is transmitted 
again and the outputs of the node are set accordingly. 