3.1.11 Technical Data 
System data 
System data ETHERNET 
  Number of controllers  Limited by ETHERNET specification 
  Transmission medium  Twisted Pair S-UTP 100 W CAT 5 
  max. length of fieldbus segment  100 m acc. to IEEE 802.3 standard 
  max. network length  acc. to IEEE 802.3 standard 
  Baud rate  10/100 Mbit/s 
  Fieldbus coupler connection  1 x RJ45, 1 x RS232 
  Protocols  BACnet/IP, BACnet PTP, MODBUS/TCP (UDP), HTTP, 
BootP, DHCP, DNS, SNTP, FTP, SNMP V1, SMTP 
Serial system data (BACnet PTP)*   * available from software version 2 
  Baud rate  9600 baud ... 115 200 baud 
  max. length of fieldbus segment  15 m depending on the baud rate / on the cable (at 19200 
baud) 
  Fieldbus coupler connection  1 x D-Sub 9 socket 
 Programming  WAGO-I/O-PRO CAA 
  IEC 61131-3-3  IL, LD, FBD (CFC), ST, FC 
  BACnet device profile  B-BC (BACnet-Building-Controller) 
Standards and regulations (see chapter 2.2) 
EMC CE Immunity to interference  in acc. with EN 61000-6-2 (2005) 
EMC CE Emission of interference  in acc. with EN 61000-6-3 (2001) +A11:2004 
Vibration resistance  acc. to IEC 60068-2-6 
Shock resistance  acc. to IEC 60068-2-27 
Degree of protection  IP 20 
Approvals (see chapter 2.2)   
C
UL
US
 (UL508) 
Conformity marking 
BACnet conformity test in preparation 
Accessories 
PC software  WAGO BACnet Configurator 
Miniature WSB Quick marking system 
Technical Data 
Number of bus modules 
with bus extension 
64 
250 
Configuration via PC 
Program memory  512 Kbytes 
Data memory  256 Kbytes 
Non-volatile memory (retain)  24 Kbytes (16 Kbytes retain, 8 Kbytes flag) 
Voltage supply  DC 24 V (-25 % ... +30 %) 
Input current 
max
  500 mA at 24 V 
Efficiency of the power supply  87 % 
Internal current consumption  300 mA at 5 V 
Total current for bus modules  1700 mA at 5 V 
Isolation  500 V system/supply 