Technical data
    BACnet/IP Controller 750-830   • 141 
    BACnet Building Controller (B-BC)   
WAGO-I/O-SYSTEM 750   
BACnet/IP Controller 
3.1.12.1.1.1  Data Sharing BIBBs 
These BIBBs prescribe the BACnet capabilities required to interoperably per-
form the data sharing functions. 
Data Sharing - ReadProperty-A (DS-RP-A) 
The A device is a user of data from device B. 
BACnet Service  Requests  Execute 
ReadProperty x  
Data Sharing-ReadProperty-B (DS-RP-B) 
The B device is a provider of data to device A. 
BACnet Service  Requests  Execute 
ReadProperty x 
Data Sharing-ReadPropertyMultiple-A (DS-RPM-A) 
The A device is a user of data from device B and requests multiple values at 
one time. 
BACnet Service  Requests  Execute 
ReadPropertyMultiple x  
Data Sharing-ReadPropertyMultiple-B (DS-RPM-B) 
The B device is a provider of data to device A and returns multiple values at 
one time. 
BACnet Service  Requests  Execute 
ReadPropertyMultiple x 
Data Sharing-WriteProperty-A (DS-WP-A) 
The A device sets a value in device B. 
BACnet Service  Requests  Execute 
WriteProperty x  