Technical data
150 •  BACnet/IP Controller 750-830 
  BACnet Building Controller (B-BC) 
 WAGO-I/O-SYSTEM 750 
BACnet/IP Controller 
3.1.12.2 "Native" Operation of the B-BC 
If the BACnet/IP Controller is switched on, not all objects that are supported 
by the system are present. In this still unconfigured state, the following objects 
are present for the connected modules: 
•  Analog Input Object 
•  Analog Output Object 
•  Binary Input Object 
•  Binary Output Object 
•  Calendar Object 
•  Device Object 
•  File Object 
•  Scheduler Object 
The analog and digital Input and Output Objects are linked with the module 
data. A configuration or programming of the controller is not necessary for the 
creation and linking of these objects in native operation. The creation of the 
objects for the connected modules takes place automatically. 
In native operation, the object name is formed from the object type, an under-
score and the instance number. For example, the instance number 2 indicates 
that this is the second created object. 
Example: 
An analog output object with an instance number of 4 receives the object 
name "AnalogOutput_4". 
Note 
A maximum of 1000 objects can be created in the 750-830 BACnet/IP Con-
troller. 
Additional Information 
In the BACnet Configurator, you have, among other things, the possibility of 
changing object names. These must be unique within a device. 
Additional Information 
You can program objects that are not automatically created in the WAGO-
I/O-PRO CAA. You can obtain additional information on the Internet under 
Documentation ! 750-830 ! Additional Information ! BACnet - Objects, 
Properties, Services 
In the following, all objects that are automatically created in the native area 
are listed. Which of these objects are actually installed depends on the con-
nected modules. 