Technical data
    BACnet/IP Controller 750-830   • 151 
    BACnet Building Controller (B-BC)   
WAGO-I/O-SYSTEM 750   
BACnet/IP Controller 
3.1.12.2.1  Analog Input Object 
The Analog Input object defines a standardized object whose properties repre-
sent the externally visible characteristics of an analog input. 
The Analog Input Object and its properties are summarized in Tab. 3-28. The 
properties are described in section 6. 
Tab. 3-28: Properties of the Analog Input Object 
Property  Data Type  Default Value  Writable via BACnet by 
means of 
Object_Identifier BACnetObjectIdentifier   -  - 
Object_Name CharacterString  Analog_Input_X - 
Object_Type BACnetObjectType  ANALOG_INPUT - 
Present_Value REAL  -  - 
Description CharacterString  *see footnote WriteProperty 
Device_Type CharacterString  ' '  WriteProperty 
Status_Flags BACnetStatusFlags  '000'  - 
Event_State BACnetEventState  State_Normal (0)  - 
Reliability BACnetReliability  0  WriteProperty 
Out_Of_Service BOOLEAN  '0'  - 
Update_Interval Unsigned  0  - 
Units BACnetEngineeringUnits NO_UNITS (95) WriteProperty 
Min_Pres_Value REAL  0  - 
Max_Pres_Value REAL  0  - 
Resolution REAL  0  - 
COV_Increment REAL  0  WriteProperty 
Time_Delay Unsigned  0  WriteProperty 
Notification_Class Unsigned  0  WriteProperty 
High_Limit REAL  0  WriteProperty 
Low_Limit REAL  0  WriteProperty 
Deadband REAL  0  WriteProperty 
Limit_Enable BACnetLimitEnable  '111'  WriteProperty 
Event_Enable BACnetEventTransitionBits '111'  WriteProperty 
Acked_Transitions BACnetEventTransitionBits '111'  - 
Notify_Type BACnetNotifyType  Alarm (0) WriteProperty 
Event_Time_Stamps  BACnetARRAY[3] for BACnet-
TimeStamp 
UNSPECIFIED - 
*corresponds to the item number of the module 