Technical data
152 •  BACnet/IP Controller 750-830 
  BACnet Building Controller (B-BC) 
 WAGO-I/O-SYSTEM 750 
BACnet/IP Controller 
3.1.12.2.2  Analog Output Object 
The Analog Output object defines a standardized object whose properties rep-
resent the externally visible characteristics of an analog output. 
The Analog Output Object and its properties are summarized in Tab. 3-29. 
The properties are described in section 6. 
Tab. 3-29: Properties of the Analog Output Object 
Property  Data type:  Default Value  Writable via BACnet by 
means of 
Object_Identifier BACnetObjectIdentifier   -  - 
Object_Name CharacterString  Analog_Output_X - 
Object_Type BACnetObjectType  ANALOG_OUTPUT - 
Present_Value REAL  -  - 
Description CharacterString  *see footnote WriteProperty 
Device_Type CharacterString  ' '  WriteProperty 
Status_Flags BACnetStatusFlags   '000'  - 
Event_State BACnetEventState  State_Normal (0)  - 
Reliability BACnetReliability  0  WriteProperty 
Out_Of_Service BOOLEAN  '0'  - 
Units BACnetEngineeringUnits NO_UNITS (95) WriteProperty 
Min_Pres_Value REAL  0  - 
Max_Pres_Value REAL  0  - 
Resolution REAL  0  - 
Priority_Array BACnetPriorityArray  -  - 
Relinquish_Default REAL  0  WriteProperty 
COV_Increment REAL  0  WriteProperty 
Time_Delay Unsigned  0  WriteProperty 
Notification_Class Unsigned  0  WriteProperty 
High_Limit REAL  0  WriteProperty 
Low_Limit REAL  0  WriteProperty 
Deadband REAL  0  WriteProperty 
Limit_Enable BACnetLimitEnable  '111'  WriteProperty 
Event_Enable BACnetEventTransitionBits '111'  WriteProperty 
Acked_Transitions BACnetEventTransitionBits '111'  - 
Notify_Type BACnetNotifyType  Alarm (0)  WriteProperty 
Event_Time_Stamps  BACnetARRAY[3] for BACnet-
TimeStamp 
UNSPECIFIED - 
*corresponds to the item number of the module 