Technical data
    BACnet/IP Controller 750-830   • 153 
    BACnet Building Controller (B-BC)   
WAGO-I/O-SYSTEM 750   
BACnet/IP Controller 
3.1.12.2.3  Binary Input Object 
The Binary Input object defines a standardized object whose properties repre-
sent the externally visible characteristics of a binary input. A "binary input" is 
a physical device or hardware input that can be in only one of two distinct 
states. In this description, those states are referred to as ACTIVE and 
INACTIVE. A typical use of a binary input is to indicate whether a particular 
piece of mechanical equipment, such as a fan or pump, is running or idle. The 
state ACTIVE corresponds to the situation when the equipment is on or run-
ning, and INACTIVE corresponds to the situation when the equipment is off 
or idle. 
In some applications, electronic circuits may reverse the relationship between 
the application-level logical states ACTIVE and INACTIVE and the physical 
state of the underlying hardware. For example, a normally open relay contact 
may result in an ACTIVE state when the relay is energized, while a normally 
closed relay contact may result in an INACTIVE state when the relay is ener-
gized. The Binary Input object provides for this possibility by including a Po-
larity property. 
The Binary Input Object and its properties are summarized in Tab. 3-30. The 
properties are described in section 6. 
Tab. 3-30: Properties of the Binary Input Object 
Property  Data type:  Default Value  Writable via BACnet by 
means of 
Object_Identifier BACnetObjectIdentifier  -  - 
Object_Name CharacterString Binary_Input_X - 
Object_Type BACnetObjectType BINARY_INPUT - 
Present_Value BACnetBinaryPV -  - 
Description CharacterString *see footnote WriteProperty 
Device_Type CharacterString ' '  WriteProperty 
Status_Flags BACnetStatusFlags '000' - 
Event_State BACnetEventState State_Normal (0)  - 
Reliability BACnetReliability 0 WriteProperty 
Out_Of_Service BOOLEAN  '0'  - 
Polarity BACnetPolarity 0 WriteProperty 
Inactive_Text CharacterString "inactive" WriteProperty 
Active_Text CharacterString "active" WriteProperty 
Change_Of_State_Time BACnetDateTime  UNSPECIFIED - 
Change_Of_State_Count Unsigned  0  - 
Time_Of_State_Count_Reset BACnetDateTime  UNSPECIFIED  - 
Elapsed_Active_Time Unsigned32  0  - 
Time_Of_Active_Time_Reset BACnetDateTime  UNSPECIFIED  - 