Technical data
158 •  BACnet/IP Controller 750-830 
  BACnet Building Controller (B-BC) 
 WAGO-I/O-SYSTEM 750 
BACnet/IP Controller 
3.1.12.2.6 Device Object 
The Device object defines a standardized object whose properties represent 
the externally visible characteristics of a BACnet Device. There shall be ex-
actly one Device object in each BACnet Device. A Device object is referenced 
by its Object_Identifier property, which is not only unique to the BACnet De-
vice that maintains this object but is also unique throughout the BACnet inter-
network. 
The Device Object and its properties are summarized in Tab. 3-33. The prop-
erties are described in section 6. 
Tab. 3-33: Properties of the Device Object 
Property  Data type:  Default Value  Writable via 
BACnet by 
means of 
Object_Identifier BACnetObjectIdentifier  -  - 
Object_Name CharacterString "Unnamed" - 
Object_Type BACnetObjectType DEVICE - 
System_Status BACnetDeviceStatus OPERATIONAL (0) - 
Vendor_Name CharacterString "WAGO Kontakttechnik 
GmbH & Co. KG" 
- 
Vendor_Identifier Unsigned16 222  - 
Model_Name CharacterString 750-830 - 
Firmware_Revision CharacterString -  - 
Application_Software_Version CharacterString  -  - 
Location CharacterString "" WriteProperty
Description CharacterString ""  WriteProperty
Protocol_Version Unsigned  -  - 
Protocol_Revision Unsigned  -  - 
Protocol_Services_Supported BACnetServicesSupported -  - 
Protocol_Object_Types_Supported BACnetObjectTypesSup-
ported 
- - 
Object_List  BACnetARRAY[N] of the 
BACnetObjectIdentifier 
- - 
Max_APDU_Length_Accepted Unsigned  1476  - 
Segmentation_Supported BACnetSegmentation SEGMENTED_BOTH (0) - 
Max_Segments_Accepted Unsigned  16  - 
Local_Time Time -  - 
Local_Date Date -  - 
UTC_Offset INTEGER 0  WriteProperty
Daylight_Savings_Status BOOLEAN  '0'  WriteProperty
APDU_Segment_Timeout Unsigned  2000  - 
APDU_Timeout Unsigned 3000  - 
Number_Of_APDU_Retries Unsigned  3  - 