Technical data
  Fieldbus Communication • 193 
  BACnet/IP 
WAGO-I/O-SYSTEM 750   
BACnet/IP Controller 
4.2.1.2.1 Objects 
BACnet offers a unified structure for different areas in the network. Thus, 
field devices such as probes, controllers of the automation level or even com-
plex control and operating stations of the management level are modeled in 
the object representation. The 25 objects are tailored specifically to the HVAC 
sector for building automation services. They contain both physical inputs and 
outputs and virtual objects. 
Tab. 4-36: BACnet objects 
Object  Function 
1  Accumulator  Count value entry; counts values 
2  Analog Input    Analog inputs, measures voltage, temperature, 
etc. 
3  Analog Output  Analog outputs, e.g. for setting controllers 
4  Analog Value  Analog value; e.g. from a calculation 
5  Averaging  Average for calculations and statistics 
6  Binary Input  Binary input, reports an event or disturbance 
7  Binary Output  Binary output; alternates between two states 
8  Binary Value    Binary value, virtual binary data time 
9  Calendar    Operating calendar, list of holidays and vacations
10  Command  (Group) request to execute predefined activities 
(e.g. a list of switching commands) 
11  Device    Device, information on the respective BACnet 
device 
12  Event Enrollment  Event category, defined reactions to events 
13  File  File, transmits data 
14  Group  Group entry, grouped object values in the device 
15  Life-Safety-Point  Hazard reporter, delivers information on proper-
ties with regard to notifications of danger 
16  Life-Safety-Zone  Security area, includes hazard reporting objects 
according to certain criteria 
17  Loop  Controller, performs regulation functions 
18  Multi-State Input  Multi-level input, delivers reports on states such 
as off/on, open/closed as a coded number 
19  Multi-State Output  Multi-level output, delivers the output states of 
commands 