Technical data
198  •  Fieldbus Communication 
 BACnet/IP 
 WAGO-I/O-SYSTEM 750 
BACnet/IP Controller 
Virtual terminal services (Virtual Terminal Service) 
•  VT-Open Service 
Establishes a connection to a network 
•  VT-Close Service 
Breaks the connection off 
•  VT-Data Service 
Transmits data between network members 
4.2.1.2.3.1 Client-Server Communication 
In Client-Server communication, Clients and Servers are considered to have 
different functions. A Clients makes a request as a service user of a Server 
(service provider). The Server then sends its response back to the Client. 
BACnet devices can work, depending on function, both as a Client and as a 
Server. For example, a device with the ReadProperty service can read a value 
in another object; in the same manner, however, a value in one of its own ob-
jects can also be changed from the outside. 
4.2.1.2.3.2 Prioritization 
Prioritization for Output Objects 
BACnet applications can access Objects through Services and change their 
properties. Access prioritization is required to regulate and organize access of 
various applications to the properties. The BACnet standard distinguishes be-
tween 16 different priority levels. 
A priority can only refer to current values (Present_Value) of output objects. 
For this reason they are also called "command properties". 
The processing sequences for individual applications can be changed using 
prioritization. Thus, the simultaneous access for several uses of the same ob-
jects is regulated (see Fig. 4-1). The use on the highest priority level with the 
lowest number has priority. 