Technical data
206  •  Fieldbus Communication 
 BACnet/IP 
 WAGO-I/O-SYSTEM 750 
BACnet/IP Controller 
Tab. 4-38: IAs/BIBBs of the six standardized device profiles 
B-OWS  B-BC  B-AAC  B-ASC  B-SA  B-SS 
IA 
Data Sharing 
DS-RP-A,B DS-RP-A,B  DS-RP-B  DS-RP-B  DS-RP-B DS-RP-B
DS-RPM-A DS-RPM-A,B DS-RPM-B DS-WP-B  DS-WP-B 
DS-WP-A DS-WP-A,B DS-WP-B 
DS-WPM-A DS-WPM-B  DS-WPM-B 
DS-COVU-A,B 
Alarm & 
AE-N-A AE-N-I-B  AE-N-I-B 
Event Mgmt 
AE-ACK-A AE-ACK-B  AE-ACK-B 
AE-INFO-A AE-INFO-B  AE-INFO-B 
AE-ESUM-A AE-ESUM-B 
Scheduling 
SCHED-A SCHED-E-B SCHED-I-B 
Trending 
T-VMT-A T-VMT-I-B 
T-ATR-A T-ATR-B 
Device & 
DM-DDB-A,B DM-DDB-A,B  DM-DDB-B  DM-DDB-B 
Network 
DM-DOB-A,B DM-DOB-A,B  DM-DOB-B  DM-DOB-B 
Mgmt 
DM-DCC-A DM-DCC-B  DM-DCC-B DM-DCC-B 
DM-TS-A DM-TS-B 
or 
DM-UTC-B 
DM-TS-B 
or 
DM-UTC-B 
DM-UTC-A 
DM-RD-A DM-RD-B  DM-RD-B 
DM-BR-A DM-BR-B 
NM-CE-A NM-CE-A 
4.2.1.2.7.1 Data Types 
Services utilize communication units, so-called "Application Layer Protocol 
Data Units" (APDUs) that are defined in an abstract ASN.8824 syntax in ac-
cordance with ISO Standard 1 to ensure uniform data transfer. Both simple 
data types like BOOLEAN, INTEGER and REAL as well as special BACnet 
data types are used. These can in turn be nested as SEQUENCE, SET, 
CHOICE, etc. 
Additional Information 
You can find the device-specific data representation of the BACnet Objects 
and Services in the documentation of the BACnet Library "BACnet_xx.lib" at 
the website http://www.wago.com under Service ! Downloads ! Building 
Automation ! BACnet Downloads ! Software 