Technical data
  Fieldbus Communication • 217 
  MODBUS Functions 
WAGO-I/O-SYSTEM 750   
BACnet/IP Controller 
4.3.3  Description of the MODBUS Functions 
All MODBUS functions are executed as follows: 
A MODBUS TCP master (e.g., a PC) makes a request to the WAGO fieldbus 
node using a specific function code based on the desired operation. The 
WAGO fieldbus node receives the datagram and then responds to the master 
with the proper data, which is based on the master’s request. 
If the WAGO fieldbus node receives an incorrect request, it sends an error 
datagram (Exception) to the master. 
The exception code contained in the exception has the following meaning: 
Exception 
Code 
Meaning 
0x01 Illegal Function 
0x02  Illegal Data Address 
0x03  Illegal Data Value 
0x04  Slave Device Failure 
0x05 Acknowledge 
0x06 Server Busy 
0x08  Memory Parity Error 
0x0A  Gateway Path Unavailable 
0x0B  Gateway Target Device Failed To Respond 
The following chapters describe the datagram architecture of request, response 
and exception with examples for each function code. 
Note 
In the case of the read functions (FC1 – FC4) the outputs can be additionally 
written and read back by adding an offset of 200
hex 
(0x0200) to the MODBUS 
addresses in the range of [0
 hex 
- FF
 hex
] and an offset of 1000
hex 
(0x01000) to the 
MODBUS addresses in the range of [6000
 hex
 - 62FC
 hex
]. 