220  •  Fieldbus Communication 
 MODBUS Functions 
 WAGO-I/O-SYSTEM 750 
BACnet/IP Controller 
4.3.3.3 Function Code FC3 (Read multiple registers) 
This function reads the contents of holding registers from a slave device in 
word format. 
Request 
The request specifies the reference number (start register) and the word count 
(register quantity) of the registers to be read. The reference number of the re-
quest is zero based, therefore, the first register starts at address 0. 
Example: Read registers 0 and 1: 
Byte  Field name  Example 
Byte 0, 1  Transaction identifier  0x0000 
Byte 2, 3  protocol identifier  0x0000 
Byte 4, 5  length field  0x0006 
Byte 6  unit identifier  0x01 not used 
Byte 7  MODBUS function code  0x03 
Byte 8, 9  reference number  0x0000 
Byte 10, 11  Word count  0x0002 
Response 
The reply register data is packed as 2 bytes per register. The first byte contains 
the higher value bits, the second the lower values. 
Byte  Field name  Example 
.....   
Byte 7  MODBUS function code  0x03 
Byte 8  Byte count  0x04 
Byte 9, 10  Value Register 0  0x1234 
Byte 11, 12  Value Register 1  0x2345 
The contents of register 0 are displayed by the value 0x1234 and the contents 
of register 1 is 0x2345. 
Exception 
Byte  Field name  Example 
.....   
Byte 7  MODBUS function code  0x83 
Byte 8  Exception code  0x01 or 0x02 