Technical data
  Fieldbus Communication • 223 
  MODBUS Functions 
WAGO-I/O-SYSTEM 750   
BACnet/IP Controller 
4.3.3.6 Function Code  FC6 (Write single register) 
This function writes the value of one single output register to a slave device in 
word format. 
Request 
The request specifies the reference number (register address) of the first out-
put word to be written. The value to be written is specified in the “Register 
Value” field. The reference number of the request is zero based; therefore, the 
first register starts at address 0. 
Example: Write a value of 0x1234 to the second output register. 
Byte  Field name  Example 
Byte 0, 1  Transaction identifier  0x0000 
Byte 2, 3  protocol identifier  0x0000 
Byte 4, 5  length field  0x0006 
Byte 6  Unit identifier  0x01 not used 
Byte 7  MODBUS function code  0x06 
Byte 8, 9  reference number  0x0001 
Byte 10, 11  Register Value  0x1234 
Response 
The reply is an echo of the inquiry. 
Byte  Field name  Example 
.....   
Byte 7  MODBUS function code  0x06 
Byte 8, 9  Reference number  0x0001 
Byte 10, 11  Register Value  0x1234 
Exception 
Byte  Field name  Example 
.....   
Byte 7  MODBUS function code  0x85 
Byte 8  Exception code  0x01 or 0x02 










