Technical data
224  •  Fieldbus Communication 
 MODBUS Functions 
 WAGO-I/O-SYSTEM 750 
BACnet/IP Controller 
4.3.3.7 Function Code FC11 (Get comm event counter) 
This function returns a status word and an event counter from the slave de-
vice’s communication event counter. By reading the current count before and 
after a series of messages, a master can determine whether the messages were 
handled normally by the slave. 
Following each successful new processing, the counter counts up. This count-
ing process is not performed in the case of exception replies, poll commands 
or counter inquiries. 
Request 
Byte  Field name  Example 
Byte 0, 1  Transaction identifier  0x0000 
Byte 2, 3  protocol identifier  0x0000 
Byte 4, 5  length field  0x0002 
Byte 6  unit identifier  0x01 not used 
Byte 7  MODBUS function code  0x0B 
Response 
The reply contains a 2-byte status word and a 2-byte event counter. The status 
word only contains zeroes. 
Byte  Field name  Example 
.....   
Byte 7  MODBUS function code  0x0B 
Byte 8, 9  Status  0x0000 
Byte 10, 11  Event Count  0x0003 
The event counter shows that 3 (0x0003) events were counted. 
Exception 
Byte  Field name  Example 
.....   
Byte 7  MODBUS function code  0x85 
Byte 8  Exception code  0x01 or 0x02 