Technical data
  Fieldbus Communication • 229 
  MODBUS Functions 
WAGO-I/O-SYSTEM 750   
BACnet/IP Controller 
4.3.4  MODBUS Register Mapping 
The following tables display the MODBUS addressing and the corresponding 
IEC61131 addressing for the process image, the PFC variables, the NOVRAM 
data, and the internal variables is represented. 
Via the register services the states of the complex and digital I/O modules can 
be determined or changed. 
Register (Word) Access Reading (with FC3, FC4 and FC23): 
MODBUS-Address IEC61131
[
dec
]
[
hex
]
Address
Memory Range 
0 
... 255 
0x0000 
... 0x00FF 
%IW0 
... %IW255 
Physical Input Area (1) 
First 256 Words of physical input data 
256 
... 511 
0x0100 
... 0x01FF 
%QW256 
... %QW511 
PFC-OUT-Area 
Volatile PFC Output variables 
512 
... 767 
0x0200 
... 0x02FF 
%QW0 
... %QW255 
Physical Output Area (1) 
First 256 Words of physical output data 
768 
... 1023 
0x0300 
... 0x03FF 
%IW256 
... %IW511 
PFC-IN-Area 
Volatile PFC Input variables 
1024 
... 4095 
0x0400 
... 0x0FFF 
-  MODBUS Exception: 
“Illegal data address” 
4096 
... 12287 
0x1000 
... 0x2FFF 
-  Configuration Register (see following Chapter 
4.3.5.3 Configuration Functions) 
12288 
... 24575 
0x3000 
... 0x5FFF 
%MW0 
... %MW12287
NOVRAM 
8kB retain memory (max. 24kB) 
24576 
... 25340 
0x6000 
... 0x62FC 
%IW512 
... %IW1275 
Physical Input Area (2) 
Additional 764 Words physical input data 
25341 
... 28671 
0x62FD 
... 0x6FFF 
-  MODBUS Exception: “ 
Illegal data address” 
28672 
... 29436 
0x7000 
... 0x72FC 
%QW512 
... %QW1275 
Physical Output Area (2) 
Additional 764 Words physical output data 
29437 
... 65535 
0x72FD 
... 0xFFFF 
-  MODBUS Exception: “ 
Illegal data address” 
Register (Word) Access Writing (with FC6, FC16, FC22 and FC23): 
MODBUS-Address IEC61131
[
dec
]
[
hex
]
Address
Memory Range 
0 
... 255 
0x0000 
... 0x00FF 
%QW0 
... %QW255 
Physical Output Area (1) 
First 256 Words of physical output data 
256 
... 511 
0x0100 
... 0x01FF 
%IW256 
... %IW511 
PFC-IN-Area 
Volatile PFC Input variables 
512 
... 767 
0x0200 
... 0x02FF 
%QW0 
... %QW255 
Physical Output Area (1) 
First 256 Words of physical output data 
768 
... 1023 
0x0300 
... 0x03FF 
%IW256 
... %IW511 
PFC-IN-Area 
Volatile PFC Input variables 
1024 
... 4095 
0x0400 
... 0x0FFF 
-  MODBUS Exception: 
“Illegal data address” 
4096 
... 12287 
0x1000 
... 0x2FFF 
-  Configuration Register (see following Chapter 
4.3.5.3 Configuration Functions) 