Technical data
230  •  Fieldbus Communication 
 MODBUS Functions 
 WAGO-I/O-SYSTEM 750 
BACnet/IP Controller 
MODBUS-Address  IEC61131
[
dec
]
[
hex
]
  Address
Memory Range 
12288 
... 24575 
0x3000 
... 0x5FFF 
%MW0 
... %MW12287
NOVRAM 
8kB retain memory (max. 24kB) 
24576 
... 25340 
0x6000 
... 0x62FC 
%QW512 
... %QW1275 
Physical Output Area (2) 
Additional 764 Words physical output data 
25341 
... 28671 
0x62FD 
... 0x6FFF 
-  MODBUS Exception: “ 
Illegal data address” 
28672 
... 29436 
0x7000 
... 0x72FC 
%QW512 
... %QW1275 
Physical Output Area (2) 
Additional 764 Words physical output data 
29437 
... 65535 
0x72FD 
... 0xFFFF 
-  MODBUS Exception: “ 
Illegal data address” 
The digital MODBUS services (coil services) are Bit accesses, with which 
only the states of digital I/O modules can be determined or changed. Complex 
I/O modules are not attainable with these services and so they are ignored. Be-
cause of this the addressing of the digital channels begins again with 0, so that 
the MODBUS address is always identical to the channel number, (i.e. the digi-
tal input no. 47 has the MODBUS address "46"). 
Bit Access Reading (with FC1 and FC2): 
MODBUS Address 
[
dec
]
[
hex
]
Memory Range  Description 
0 
... 511 
0x0000 
... 0x01FF 
Physical Input Area (1) 
First 512 digital inputs 
512 
... 1023 
0x0200 
... 0x03FF 
Physical Output Area (1)  First 512 digital outputs 
1024 
... 4095 
0x0400 
... 0x0FFF 
-  MODBUS Exception: 
“Illegal data address” 
4096 
... 8191 
0x1000 
... 0x1FFF 
%QX256.0 
...%QX511.15 
PFC-OUT-Area 
Volatile PFC Output variables 
8192 
... 12287 
0x2000 
... 0x2FFF 
%IX256.0 
...%IX511.15 
PFC-IN-Area 
Volatile PFC Input variables 
12288 
... 32767 
0x3000 
... 0x7FFF 
%MX0 
... %MX1279.15 
NOVRAM 
8kB retain memory (max. 24kB) 
32768 
... 34295 
0x8000 
... 0x85F7 
Physical Input Area (2)  Starts with the 513
th
 and ends with 
the 2039
th
 digital input 
34296 
... 36863 
0x85F8 
... 0x8FFF 
  MODBUS Exception: 
“Illegal data address” 
36864 
... 38391 
0x9000 
... 0x95F7 
Physical Output Area (2)  Starts with the 513
th
 and ends with 
the 2039
th
 digital output 
38392 
... 65535 
0x95F8 
... 0xFFFF 
  MODBUS Exception: 
“Illegal data address” 










