Technical data
  Fieldbus Communication • 237 
  MODBUS Functions 
WAGO-I/O-SYSTEM 750   
BACnet/IP Controller 
Register address 0x100B 
Value  Save Watchdog Parameter 
Access write 
Default 0x0000 
Description  With writing of '1' in register 0x100B 
the registers 0x1000, 0x1001, 0x1002 are set on remanent. 
4.3.5.2 Diagnostic Functions 
The following registers can be read to determine errors in the node: 
Register address 0x1020 (MODBUS Address 404129) 
Designation LedErrCode 
Access read 
Description  Declaration of the Error code (see section 3.1.8.4 for error code definitions) 
Register address 0x1021 (MODBUS Address 404130) 
Designation LedErrArg 
Access read 
Description  Declaration of the Error argument (see section 3.1.8.4 for error code defini-
tions) 
4.3.5.3 Configuration Functions 
The following registers contain configuration information of the connected 
modules: 
Register address 0x1022 (MODBUS Address 404131) 
Designation CnfLen.AnalogOut 
Access read 
Description  Number of word-based outputs registers in the process image in bits (divide 
by 16 to get the total number of analog words) 
Register address 0x1023 (MODBUS Address 404132) 
Designation CnfLen.AnalogInp 
Access read 
Description  Number of word-based inputs registers in the process image in bits (divide 
by 16 to get the total number of analog words) 