Technical data
238  •  Fieldbus Communication 
 MODBUS Functions 
 WAGO-I/O-SYSTEM 750 
BACnet/IP Controller 
Register address 0x1024 (MODBUS Address 404133) 
Designation CnfLen.DigitalOut 
Access read 
Description  Number of digital output bits in the process image 
Register address 0x1025 (MODBUS Address 404134) 
Designation CnfLen.DigitalInp 
Access read 
Description  Number of digital input bits in the process image 
Register address 0x1028 (MODBUS Address 404137) 
Designation Boot options 
Access  read / write 
Description Boot configuration: 
1: BootP 
2: DHCP 
4: EEPROM 
Register address 0x1029 (MODBUS Address 404138, with 9 words) 
Designation  MODBUS TCP statistics 
Access  read / write 
Description  1 word SlaveDeviceFailure  !  internal bus error, F-bus error 
by activated watchdog 
1 word BadProtocol;  !  error in the MODBUS TCP 
header 
1 word BadLength;   !  Wrong telegram length 
1 word BadFunction;  !  Invalid function code 
1 word BadAddress;  !  Invalid register address 
1 word BadData;    ! Invalid value 
1 word TooManyRegisters;  !  Number of the registers which 
can be worked on is too large, Read/Write 125/100 
1 word TooManyBits ! Number of the coils which can 
be worked on is too large, Read/Write 2000/800 
1 word ModTcpMessageCounter ! Number of received 
       MODBUS/TCP requests 
With Writing 0xAA55 or 0x55AA in the register will reset this data area. 










