Technical data
240  •  Fieldbus Communication 
 MODBUS Functions 
 WAGO-I/O-SYSTEM 750 
BACnet/IP Controller 
Examples: 
4 Channel Digital Input Module = 0x8401 
bit 15 1
4 
1
3 
1
2 
1
1 
10 9 8 7 6 5 4 3 2 1 0 
code 1  0 0 0 0 1 0 0 0 0 0 0 0 0 0 1 
hex 8  4  0  1 
2 Channel Digital Output Module = 0x8202 
bit 1
5 
1
4 
1
3 
12 11 10 9 8 7 6 5 4 3 2 1 0 
code 1 0 0 0 0 0 1 0 0 0 0 0 0 0 1 0 
hex 8  2  0  2 
Register address 0x2031 (MODBUS Address 408242, with a word count of up to 64) 
Designation  Description of the connected busmodules 
Access  read modules 65 ... 128 
Description  Length 1-64 words 
These 64 registers identify the 2nd block of I/O modules present (modules 
65 to 128). Each module is represented in a word. Because item numbers 
cannot be read out of digital modules, a code is displayed for them, as de-
fined below: 
Bit position 0    ! Input module 
Bit position 1    ! Output module 
Bit position 2-7    ! not used 
Bit position 8-14    !  module size in bits 
Bit position 15    !  Designation digital module 
Register address 0x2032 (MODBUS Address 408243, with a word count of up to 64) 
Designation  Description of the connected I/O modules 
Access  read modules 129 ... 192 
Description  Length 1-64 words 
These 64 registers identify the 3rd block of I/O modules present (modules 
129 to 192). Each module is represented in a word. Because item numbers 
cannot be read out of digital modules, a code is displayed for them, as de-
fined below: 
Bit position 0    ! Input module 
Bit position 1    ! Output module 
Bit position 2-7    ! not used 
Bit position 8-14    !  module size in bits 
Bit position 15    !  Designation digital module 