Technical data
  Fieldbus Communication • 241 
  MODBUS Functions 
WAGO-I/O-SYSTEM 750   
BACnet/IP Controller 
Register address 0x2033 (MODBUS Address 408244, with a word count of up to 63) 
Designation  Description of the connected I/O modules 
Access  Read modules 193 ... 255 
Description  Length 1-63 words 
These 63 registers identify the 4th block of I/O modules present (modules 
193 to 255). Each module is represented in a word. Because item numbers 
cannot be read out of digital modules, a code is displayed for them, as de-
fined below: 
Bit position 0    ! Input module 
Bit position 1    ! Output module 
Bit position 2-7    ! not used 
Bit position 8-14    !  module size in bits 
Bit position 15    !  Designation digital module 
Register address 0x2040 (MODBUS Address 408257) 
Designation  Implement a software reset 
Access  write (Write sequence 0xAA55 or 0x55AA) 
Description  With Writing 0xAA55 or 0x55AA the register will be reset. 
Register address 0x2041 (MODBUS Address 408258)  since Firmware version 3 
Designation Flash Format 
Access  write (Write sequence 0xAA55 or 0x55AA) 
Description  The file system Flash is again formatted. 
Register address 0x2042 (MODBUS Address 408259)  since Firmware version 3 
Designation  Extract data files 
Access  write (Write sequence 0xAA55 or 0x55AA) 
Description  The standard files (HTML pages) of the Controller are extracted and writ-
ten into the Flash. 
Register address 0x2043 since Firmware version 9 
Designation 0x55AA 
Access write 
Description Factory Settings 