Technical data
242  •  Fieldbus Communication 
 MODBUS Functions 
 WAGO-I/O-SYSTEM 750 
BACnet/IP Controller 
4.3.5.4 Firmware Information 
The following registers contain information on the firmware of the controller: 
Register address 0x2010 (MODBUS Address 408209, with a word count of 1) 
Designation Revision, INFO_REVISION 
Access Read 
Description  Firmware Index, e. g. 0005 for version 5 
Register address 0x2011 (MODBUS Address 408210, with a word count of 1) 
Value  Series code, INFO_SERIES 
Access Read 
Description  WAGO serial number, e. g. 0750 for WAGO-I/O-SYSTEM 750 
Register address 0x2012 (MODBUS Address 408211, with a word count of 1) 
Value  Item number, INFO_ITEM 
Access Read 
Description  WAGO item number, e. g. 841 for the controller 
Register address 0x2013 (MODBUS Address 408212, with a word count of 1) 
Value  Major sub item code, INFO_MAJOR 
Access read 
Description  Firmware version Major Revision 
Register address 0x2014 (MODBUS Address 408213, with a word count of 1) 
Value  Minor sub item code, INFO_MINOR 
Access read 
Description  Firmware version Minor Revision 
Register address 0x2020 (MODBUS Address 408225, with a word count of up to 16) 
Value Description, INFO_DESCRIPTION 
Access Read 
Description  Information on the controller, 16 words 