Technical data
  Fieldbus Communication • 243 
  MODBUS Functions 
WAGO-I/O-SYSTEM 750   
BACnet/IP Controller 
Register address 0x2021 (MODBUS Address 408226, with a word count of up to 8) 
Value Description, INFO_DESCRIPTION 
Access Read 
Description  Time of the firmware version, 8 words 
Register address 0x2022 (MODBUS Address 408227, with a word count of up to 8) 
Value Description, INFO_DATE 
Access Read 
Description  Date of the firmware version, 8 words 
Register address 0x2023 (MODBUS Address 408228, with a word count of up to 32) 
Value Description, INFO_LOADER_INFO 
Access read 
Description  Information to the programming of the firmware, 32 words 
4.3.5.5 Constant Registers 
The following registers contain constants, which can be used to test communi-
cation with the master: 
Register address 0x2000 (MODBUS Address 408193) 
Value Zero, GP_ZERO 
Access Read 
Description  Constant with zeros 
Register address 0x2001 (MODBUS Address 408194) 
Value Ones, GP_ONES 
Access Read 
Description  Constant with ones. Is –1 if this is declared as "signed int" or MAXVALUE 
if it is declared as "unsigned int". 
Register address 0x2002 (MODBUS Address 408195) 
Value 1,2,3,4, GP_1234 
Access Read 
Description  This constant value is used to test the Intel/Motorola format specifier. If the 
master reads a value of 0x1234, then with Intel format is selected – this is 
the correct format. If 0x3412 appears, Motorola format is selected. 