Technical data
244  •  Fieldbus Communication 
 MODBUS Functions 
 WAGO-I/O-SYSTEM 750 
BACnet/IP Controller 
Register address 0x2003 (MODBUS Address 408196) 
Value  Mask 1, GP_AAAA 
Access Read 
Description  This constant is used to verify that all bits are accessible to the fieldbus 
master. This will be used together with register 0x2004. 
Register address 0x2004 (MODBUS Address 408197) 
Value  Mask 1, GP_5555 
Access Read 
Description  This constant is used to verify that all bits are accessible to the fieldbus 
master. This will be used together with register 0x2003. 
Register address 0x2005 (MODBUS Address 408198) 
Value  Maximum positive number, GP_MAX_POS 
Access Read 
Description  Constant in order to control arithmetic. 
Register address 0x2006 (MODBUS Address 408199) 
Value  Maximum negative number, GP_MAX_NEG 
Access Read 
Description  Constant in order to control arithmetic. 
Register address 0x2007 (MODBUS Address 408200) 
Value  Maximum half positive number, GP_HALF_POS 
Access Read 
Description  Constant in order to control arithmetic. 
Register address 0x2008 (MODBUS Address 408201) 
Value  Maximum half negative number, GP_HALF_NEG 
Access Read 
Description  Constant in order to control arithmetic. 
Register address 0x3000 to 0x5FFF (MODBUS Address 412289 to 424576) 
Value Retain range 
Access read/write 
Description  These registers can be accessed as the flag/retain range. 