Technical data
260 •  I/O Modules 
  Process Data Architecture for MODBUS/TCP 
 WAGO-I/O-SYSTEM 750 
BACnet/IP Controller 
5.2.3  Analog Input Modules 
The hardware of an analog input module has 16 bits of measured analog data 
per channel and 8 bits of control/status. However, the coupler/controller with 
MODBUS/TCP does not have access to the 8 control/status bits. Therefore, 
the coupler/controller with MODBUS/TCP can only access the 16 bits of ana-
log data per channel, which are grouped as words and mapped in Intel format 
in the Input Process Image. 
When digital input modules are also present in the node, the analog input data 
is always mapped into the Input Process Image in front of the digital data. 
1 Channel Analog Input Module 
750-491, (and all variations) 
Input Process Image 
Byte Destination 
Offset 
High Byte  Low Byte 
Remark 
0  D1  D0  Measured Value U
D
1  D3  D2  Measured Value U
ref
2 Channel Analog Input Modules 
750-452, -454, -456, -461, -462, -465, -466, -467, -469, -472, -474, -475, -476, 
-477, -478, -479, -480, -481, -483, -485, -492, (and all variations), 
753-452, -454, -456, -461, -465, -466, -467, -469, -472, -474, -475, -476, -477, 
-478, -479, -483, -492, (and all variations) 
Input Process Image 
Byte Destination 
Offset 
High Byte  Low Byte 
Remark 
0  D1  D0  Measured Value Channel 1 
1  D3  D2  Measured Value Channel 2 