Technical data
  I/O Modules   • 263 
    Process Data Architecture for MODBUS/TCP   
WAGO-I/O-SYSTEM 750   
BACnet/IP Controller 
Input Process Image 
Byte Destination 
Offset 
High Byte  Low Byte 
Remark 
0 -  S  Status byte 
1 D1  D0 
2 D3  D2 
Counter Value 
Output Process Image 
Byte Destination 
Offset 
High Byte  Low Byte 
Remark 
0 -  C  Control byte 
1 D1  D0 
2 D3  D2 
Counter Setting Value 
750-404/000-005 
The above Counter Modules have a total of 5 bytes of user data in both the In-
put and Output Process Image (4 bytes of counter data and 1 byte of con-
trol/status). The two counter values are supplied as 16 bits. The following ta-
bles illustrate the Input and Output Process Image, which has a total of 3 
words mapped into each image. Word alignment is applied. 
Input Process Image 
Byte Destination 
Offset 
High Byte  Low Byte 
Remark 
0 -  S  Status byte 
1  D1  D0  Counter Value of Counter 1 
2  D3  D2  Counter Value of Counter 2 
Output Process Image 
Byte Destination 
Offset 
High Byte  Low Byte 
Remark 
0 -  C  Control byte 
1 D1  D0 Counter Setting Value of Counter 1 
2 D3  D2 Counter Setting Value of Counter 2 










