Technical data
  I/O Modules   • 265 
    Process Data Architecture for MODBUS/TCP   
WAGO-I/O-SYSTEM 750   
BACnet/IP Controller 
Pulse Width Modules 
750-511, (and all variations) 
The above Pulse Width modules have a total of 6 bytes of user data in both the 
Input and Output Process Image (4 bytes of channel data and 2 bytes of con-
trol/status). The two channel values are supplied as 16 bits. Each channel has 
its own control/status byte. The following table illustrates the Input and Out-
put Process Image, which has a total of 4 words mapped into each image. 
Word alignment is applied. 
Input and Output Process Image 
Byte Destination 
Offset 
High Byte  Low Byte 
Remark 
0  -  C0/S0  Control/Status byte of Channel 1 
1  D1  D0  Data Value of Channel 1 
2  -  C1/S1  Control/Status byte of Channel 2 
3  D3  D2  Data Value of Channel 2 
Serial Interface Modules with alternative Data Format 
750-650, (and the variations /000-002, -004, -006, -009, -010, -011, -012, 
  -013) 
750-651, (and the variations /000-002, -003) 
750-653, (and the variations /000-002, -007) 
Note 
With the freely parametrizable variations /003 000 of the serial interface 
modules, the desired operation mode can be set. Dependent on it, the 
process image of these modules is then the same, as from the appropriate 
variation. 
The above Serial Interface Modules with alternative data format have a total 
of 4 bytes of user data in both the Input and Output Process Image (3 bytes of 
serial data and 1 byte of control/status). The following table illustrates the In-
put and Output Process Image, which have a total of 2 words mapped into 
each image. Word alignment is applied. 
Input and Output Process Image 
Byte Destination 
Offset 
High Byte  Low Byte 
Remark 
0  D0  C/S  Data byte  Control/Status byte 
1 D2  D1  Data bytes 










