Technical data
268 •  I/O Modules 
  Process Data Architecture for MODBUS/TCP 
 WAGO-I/O-SYSTEM 750 
BACnet/IP Controller 
750-634 
The above Incremental Encoder Interface module has 5 bytes of input data (6 
bytes in cycle duration measurement mode) and 3 bytes of output data. The 
following tables illustrate the Input and Output Process Image, which has 4 
words mapped into each image. Word alignment is applied. 
Input Process Image 
Byte Destination 
Offset 
High Byte  Low Byte 
Remark 
0  -  S  not used  Status byte 
1 D1 D0  Counter word 
2 - (D2)*
)
  not used  (Periodic time) 
3 D4 D3  Latch word 
*
) 
If cycle duration measurement mode is enabled in the control byte, the cycle 
 duration is given as a 24-bit value that is stored in D2 together with D3/D4. 
Output Process Image 
Byte Destination 
Offset 
High Byte  Low Byte 
Remark 
0  -  C  not used  Control byte 
1  D1  D0  Counter Setting word 
2 -  - 
3 -  - 
not used 
750-637 
The above Incremental Encoder Interface Module has a total of 6 bytes of user 
data in both the Input and Output Process Image (4 bytes of encoder data and 
2 bytes of control/status). The following table illustrates the Input and Output 
Process Image, which have 4 words mapped into each image. Word alignment 
is applied. 
Input and Output Process Image 
Byte Destination 
Offset 
High Byte  Low Byte 
Remark 
0  -  C0/S0  Control/Status byte of Channel 1 
1  D1  D0  Data Value of Channel 1 
2  -  C1/S1  Control/Status byte of Channel 2 
3  D3  D2  Data Value of Channel 2 










