Technical data
  I/O Modules   • 269 
    Process Data Architecture for MODBUS/TCP   
WAGO-I/O-SYSTEM 750   
BACnet/IP Controller 
750-635, 753-635 
The above Digital Pulse Interface module has a total of 4 bytes of user data in 
both the Input and Output Process Image (3 bytes of module data and 1 byte of 
control/status). The following table illustrates the Input and Output Process 
Image, which have 2 words mapped into each image. Word alignment is ap-
plied. 
Input and Output Process Image 
Byte Destination 
Offset 
High Byte  Low Byte 
Remark 
0  D0  C0/S0  Data byte  Control/Status byte 
1 D2  D1  Data bytes 
RTC Module 
750-640 
The RTC Module has a total of 6 bytes of user data in both the Input and Out-
put Process Image (4 bytes of module data and 1 byte of control/status and 1 
byte ID for command). The following table illustrates the Input and Output 
Process Image, which have 3 words mapped into each image. Word alignment 
is applied. 
Input and Output Process Image 
Byte Destination 
Offset 
High Byte  Low Byte 
Remark 
0  ID  C/S  Command byte  Control/Status byte
1 D1  D0 
2 D3  D2 
Data bytes 
DALI/DSI Master Module 
750-641 
The DALI/DSI Master module has a total of 6 bytes of user data in both the 
Input and Output Process Image (5 bytes of module data and 1 byte of con-
trol/status). The following tables illustrate the Input and Output Process Im-
age, which have 3 words mapped into each image. Word alignment is applied. 