Technical data
274 •  I/O Modules 
  Process Data Architecture for MODBUS/TCP 
 WAGO-I/O-SYSTEM 750 
BACnet/IP Controller 
5.2.6 System Modules 
System Modules with Diagnostics 
750-610, -611 
The 750-610 and 750-611 Supply Modules provide 2 bits of diagnostics in the 
Input Process Image for monitoring of the internal power supply. 
Input Process Image 
Bit 7  Bit 6  Bit 5  Bit 4  Bit 3  Bit 2  Bit 1  Bit 0 
    Diagnostic bit S 2
Fuse 
Diagnostic bit S 1
Voltage 
Binary Space Module 
750-622 
The Binary Space Modules 750-622 behave alternatively like 2 channel digital 
input modules or output modules and seize depending upon the selected set-
tings 1, 2, 3 or 4 bits per channel. According to this, 2, 4, 6 or 8 bits are occu-
pied then either in the process input or the process output image. 
Input or Output Process Image 
Bit 7  Bit 6  Bit 5  Bit 4  Bit 3  Bit 2  Bit 1  Bit 0 
 (Data bit
DI 8) 
(Data bit 
DI 7) 
(Data bit
DI 6) 
(Data bit
DI 5) 
(Data bit
DI 4) 
(Data bit
DI 3) 
Data bit 
DI 2 
Data bit
DI 1 