Technical data
276 •  List of all BACnet Properties in Native Operation 
 Acked_Transitions 
 WAGO-I/O-SYSTEM 750 
BACnet/IP Controller 
The difference between the properties "BACnetARRAY" and "List of" is that 
the elements of a field can be individually accessed through a field index 
while this is not possible for the elements of a "List of". Furthermore, the 
number of elements of a "BACnetARRAY" can be determined by reading the 
field index 0; the number of elements in a "List of" can only be determined by 
reading the whole value of the property and conducting a count. 
In the following list, the associated BACnet data type is indicated for each 
property. Under "Object", all objects in which the respective property occurs 
are listed. The description explains functions and interrelationships of the 
properties in question. If the meanings of the properties are different for dif-
ferent objects, the explanations for these objects are given separately. 
6.1 Acked_Transitions 
Data Type BACnetEventTransitionBits 
Object     Binary Input, Binary Output, Analog Input, Analog 
  Output 
Description  This property of the type BACnetEventTransitionBits 
transmits three flags that indicate the receipt of the confir-
mation for TO-OFFNORMAL, TO-FAULT and TO-
NORMAL events. In the context of the Analog Input ob-
jects, transitions the High_Limit and Low_Limit 
Event_States are considered to be OFFNORMAL events. 
The flags are deleted after the corresponding event has 
taken place and set under the following conditions: 
•  upon receipt of the corresponding acknowledgment; 
•  upon the occurrence of the event if the correspond-
ing flag is not set in the Event_Enable property 
(meaning event notifications will not be generated 
for this condition and thus no acknowledgment is 
expected); 
•  upon the occurrence of the event if the correspond-
ing flag is set in the Event_Enable property and the 
corresponding flag in the Ack_Required property of 
the Notification Class object implicitly referenced by 
the Notification_Class property of this object is not 
set (meaning no acknowledgment is expected). 
This property is required if intrinsic reporting is sup-
ported by this object. 