Technical data
278 •  List of all BACnet Properties in Native Operation 
 Alarm_Value 
 WAGO-I/O-SYSTEM 750 
BACnet/IP Controller 
6.4 Alarm_Value 
Data Type BACnetBinaryPV 
Object    Binary input 
Description  This property, of the type BACnetBinaryPV, specifies the 
value that the Present_Value property must have before an 
event is generated. This property is required if intrinsic re-
porting is supported by this object. 
Conditions for Generating a TO-OFFNORMAL Event 
A TO-OFFNORMAL event is generated under these condi-
tions: 
•  the Present_Value must maintain the value specified 
by Alarm_Value for a minimum period of time, 
specified in the Time_Delay property, and 
•  the TO-OFFNORMAL flag must be enabled in the 
Event_Enable property. 
Conditions for Generating a TO-NORMAL Event 
Once equal, the Present_Value must become not equal to 
this property before a TO-NORMAL event is generated un-
der these conditions: 
•  the Present_Value must remain not equal to the 
Alarm_Value for a minimum period of time, speci-
fied by the Time_Delay property, and 
•  the TO-NORMAL flag must be enabled in the 
Event_Enable property. 