Technical data
    List of all BACnet Properties in Native Operation   • 281 
  Change_Of_State_Count 
WAGO-I/O-SYSTEM 750   
BACnet/IP Controller 
6.10 Change_Of_State_Count 
Data Type  Unsigned 
Objects     Binary input, Binary output 
Description  This property, of the type Unsigned, represents the number 
of times that the Present_Value property has changed state 
since the Change_Of_State_Count property was most re-
cently set to a zero value. The Change_Of_State_Count 
property has a range of from 0 to 65535 or greater. A 
"change of state" is defined as any event that alters the Pre-
sent_Value property. 
Binary Input: 
When Out_Of_Service is FALSE, a change to the Polarity 
property changes the Present_Value property and is there-
fore considered a change of state. When Out_Of_Service is 
TRUE, changes to Polarity do not cause changes of state. If 
one of the optional properties Change_Of_State_Time, 
Change_Of_State_Count, or Time_Of_State_Count_Reset 
is present, then all of these properties must be present. 
Binary Output: 
A change in the Polarity property is not regarded as a 
change of state. If one of the optional properties 
Change_Of_State_Time, Change_Of_State_Count, or 
Time_Of_State_Count_Reset is present, then all of these 
properties must be present. 
6.11 Change_Of_State_Time 
Data Type BACnetDateTime 
Objects     Binary input, Binary output 
Description  This property, of the type BACnetDateTime, represents the 
date and time at which the most recent change of state oc-
curred. A "change of state" is defined as any event that al-
ters the Present_Value property. 
Binary Input: 
When Out_Of_Service is FALSE, a change to the Polarity 
property changes the Present_Value property is therefore 
considered a change of state. When Out_Of_Service is 
TRUE, changes to Polarity shall not cause changes of state. 
If one of the optional properties Change_Of_State_Time, 










