Technical data
282 •  List of all BACnet Properties in Native Operation 
 Configuration_Files 
 WAGO-I/O-SYSTEM 750 
BACnet/IP Controller 
Change_Of_State_Count, or Time_Of_State_Count_Reset 
is present, then all of these properties must be present. 
Binary Output: 
A change in polarity does not lead to a change in state. If 
one of the optional properties Change_Of_State_Time, 
Change_Of_State_Count, or Time_Of_State_Count_Reset 
is present, then all of these properties must be present. 
6.12 Configuration_Files 
Date Type  BACnetARRAY[N] for BACnetObjectIdentifier 
Objects  Device 
Description  This property is a BACnet field for BACnetObjectIdentifier. 
Entries in the array identify the files within the device that 
define the device's image that can be backed up. The content 
of this property is only required to be valid during the 
backup procedure. 
6.13 COV_Increment 
Data Type  REAL 
Objects    Analog input, Analog output 
Description  This property of the type REAL specifies the minimum 
change in the property Present_Value that will cause a 
COVNotification to be issued to subscriber COV-clients. 
This property is required if COV reporting is supported by 
this object. 
6.14 Database_Revision 
Data Type  Unsigned 
Objects  Device 
Description  This property, of type Unsigned, is a logical revision num-
ber for the device's database. It is incremented when an ob-
ject is created, an object is deleted, an object's name is 
changed, an object's Object_Identifier property is changed, 
or a restore is performed. 