Technical data
284 •  List of all BACnet Properties in Native Operation 
 Description 
 WAGO-I/O-SYSTEM 750 
BACnet/IP Controller 
•  the Present_Value must fall below the High_Limit 
minus Deadband, and 
•  the Present_Value must exceed the Low_Limit plus 
the Deadband, and 
•  the Present_Value must remain within this range for 
a minimum period of time, specified in the 
Time_Delay property, and 
•  either the HighLimitEnable or LowLimitEnable flag 
must be set in the Limit_Enable property, and 
•  the TO-NORMAL flag must be enabled in the 
Event_Enable property. 
This property is required if intrinsic reporting is supported 
by this object. 
6.18 Description 
Data Type CharacterString 
Objects  File, Binary input, Binary output, Analog input, Analog out-
put, Device, Calendar, Scheduler 
Description  This property, of type CharacterString, is a string of print-
able characters that may be used to describe the application 
being carried out by the BACnet Device or other locally de-
sired descriptive information. 
6.19 Device_Address_Binding 
Data Type  List of BACnetAddressBinding 
Objects  Device 
Description  The Device_Address_Binding property is a List of 
BACnetAddressBinding each of which consists of a 
BACnet Object_Identifier of a BACnet Device object and a 
BACnet device address in the form of a BACnetAddress. 
Entries in the list identify the actual device addresses that 
will be used when the remote device must be accessed via a 
BACnet service request. A value of zero is used for the net-
work number portion of BACnetAddress entries for other 
devices residing on the same network as this device. The list 