Technical data
    List of all BACnet Properties in Native Operation   • 285 
  Device_Type 
WAGO-I/O-SYSTEM 750   
BACnet/IP Controller 
may be empty if no device identifier-device address bind-
ings are currently known to the device. 
6.20 Device_Type 
Data Type CharacterString 
Objects    Binary Input, Binary Output, Analog Input, Analog Output 
Description  This property, of type CharacterString, is a text description 
of the physical device connected to a binary input, binary 
output, analog input or analog output. It will typically be 
used to describe the type of device attached to this in-
put/output. 
6.21 Effective_Period 
Data Type BACnetDateRange 
Objects  Scheduler 
Description  This property specifies the range of dates within which the 
Schedule object is active. Seasonal scheduling may be 
achieved by defining several Schedule Objects with non-
overlapping Effective_Periods to control the same property 
references. Upon entering its effective period, the object cal-
culates its Present_Value and returns this value to all mem-
bers of the List_Of_Object_Property_References property. 
An error writing to any member of the list does not stop the 
Schedule Object from writing to the remaining members. 
6.22 Elapsed_Active_Time 
Data Type  Unsigned32 
Objects    Binary input, Binary output 
Description  This property, of type Unsigned32, represents the accumu-
lated number of seconds that the Present_Value property has 
had the value ACTIVE since the Elapsed_Active_Time 
property was most recently set to a zero value.   