286 •  List of all BACnet Properties in Native Operation 
 Event_Enable 
 WAGO-I/O-SYSTEM 750 
BACnet/IP Controller 
6.23 Event_Enable 
Data Type BACnetEventTransitionBits 
Objects    Binary Input, Binary Output, Analog Input, Analog Output 
Description  This property, of type BACnetEventTransitionBits, shall 
convey three flags that separately enable and disable report-
ing of TO-OFFNORMAL, TO-FAULT, and TO-NORMAL 
events. In the context of Analog Input objects, transitions to 
High_Limit and Low_Limit Event_States are considered to 
be "offnormal" events. 
6.24 Event_State 
Data Type  BACnetEventState 
Objects    Binary Input, Binary Output, Analog Input, Analog Output 
Description  The Event_State property, of type BACnetEventState, is in-
cluded in order to provide a way to determine if this object 
has an active event state associated with it. If the object sup-
ports intrinsic reporting, then the Event_State property indi-
cates the event state of the object. If the object does not sup-
port intrinsic reporting, then the value of this property shall 
be NORMAL. If the Reliability property is present and does 
not have the value NO_FAULT_DETECTED, then the 
value of the Event_State property is FAULT. A change in 
the Event_State property to the value FAULT is considered 
a Fault Event. 
6.25 Event_Time_Stamps 
Data Type  BACnetARRAY[3] of BACnetTimeStamp 
Objects    Binary Input, Binary Output, Analog Input, Analog Output 
Description  This optional property, of type BACnetARRAY[3] of 
BACnetTimeStamp conveys the times of the last event noti-
fications for TO-OFFNORMAL, TO-FAULT, and TO-
NORMAL events. Time stamps of type Time or Date must 
have 'FF' in each octet and Sequence number time stamps 
must have the value 0 if no event notification of that type 
has been generated since the object was created. 