Technical data
  Mechanical Setup • 29 
  Wire Connection 
WAGO-I/O-SYSTEM 750   
BACnet/IP Controller 
2.6.9 Wire Connection 
All components have CAGE CLAMP® connections. 
The WAGO CAGE CLAMP® connection is appropriate for solid, stranded 
and finely stranded conductors. Each clamping unit accommodates one con-
ductor. 
Fig. 2-9: CAGE CLAMP® Connection  g0xxx08x 
The operating tool is inserted into the opening above the connection. This 
opens the CAGE CLAMP
®
. Subsequently the conductor can be inserted into 
the opening. After removing the operating tool, the conductor is safely 
clamped. 
More than one conductor per connection is not permissible. If several conduc-
tors have to be made at one connection point, then they should be made away 
from the connection point using WAGO Terminal Blocks. The terminal blocks 
may be jumpered together and a single wire brought back to the I/O module 
connection point. 
Attention 
If it is unavoidable to jointly connect 2 conductors, then a ferrule must be used 
to join the wires together. 
Ferrule: 
 Length      8 mm 
 Nominal cross section 
max.
 1 mm
2
 for 2 conductors with 0.5 mm
2
 each 
 WAGO Product    216-103 or products with comparable properties 