290 •  List of all BACnet Properties in Native Operation 
 Inactive_Text 
 WAGO-I/O-SYSTEM 750 
BACnet/IP Controller 
6.33 Inactive_Text 
Data Type CharacterString 
Objects    Binary input, Binary output 
Description  Binary Input: 
This property, of type CharacterString, characterizes the in-
tended effect of the INACTIVE state of the Present_Value 
property from the human operator's viewpoint. 
The content of this string is determined locally, but it is in-
tended to contain a description of the ACTIVE state that can 
be read by the user. For example, if the physical input is 
connected to a switch contact, then the Inactive_Text prop-
erty might be assigned a value such as "Fan 1 Off". If either 
the Inactive_Text property or the Active_Text property are 
present, then both of them shall be present. 
  Binary Output: 
This property, of the type CharacterString, characterizes the 
intended effect, from the human operator's viewpoint, of the 
INACTIVE state of the Present_Value property on the final 
device that is ultimately controlled by the output. The con-
tent of this character string is locally determined, but it is in-
tended to contain description of the INACTIVE state that 
can be read by the user. For example, if the physical output 
is a relay contact that turns on a light, then the Inactive_Text 
property might be assigned a value such as "Light Off". If 
one of the optional properties Inactive_Text or Active_Text 
is present, then both of these properties must be present. 
6.34 Last_Restore_Time 
Data Type BACnetTimeStamp 
Objects  Device 
Description  This optional property, of type BACnetTimeStamp, is the 
time at which the device's image was last restored. 