Technical data
    List of all BACnet Properties in Native Operation   • 291 
  Limit_Enable 
WAGO-I/O-SYSTEM 750   
BACnet/IP Controller 
6.35 Limit_Enable 
Data Type  BACnetLimitEnable 
Objects    Analog input, Analog output 
Description  This property, of type BACnetLimitEnable, shall convey 
two flags that separately enable and disable reporting of 
high limit and low limit offnormal events and their return to 
normal. This property is required if intrinsic reporting is 
supported by this object. 
6.36 List_Of_Object_Property_References 
Data Type  List of BACnetDeviceObjectPropertyReference 
Objects  Scheduler 
Description  This property specifies the Device Identifiers, Object Identi-
fiers and Property Identifiers of the properties to be written 
with specific values at specific times on specific days. 
If this property is writable, it may be restricted to only sup-
port references to objects inside of the device containing the 
Schedule object. If the property is restricted to referencing 
objects within the containing device, an attempt to write a 
reference to an object outside the containing device into this 
property shall cause a Result(-) to be returned with an error 
class of PROPERTY and an error code of 
OPTIONAL_FUNCTIONALITY_NOT_SUPPORTED. 
If this property is set to reference an object outside the de-
vice containing the Schedule object, the method used for 
writing to the referenced property value for the purpose of 
controlling the property is a local matter. The only restric-
tion on the method of writing to the referenced property is 
that the scheduling device be capable of using WriteProp-
erty for this purpose so as to be interoperable with all 
BACnet devices. 