    List of all BACnet Properties in Native Operation   • 293 
  Max_APDU_Length_Accepted 
WAGO-I/O-SYSTEM 750   
BACnet/IP Controller 
6.41 Max_APDU_Length_Accepted 
Data Type  Unsigned 
Objects  Device 
Description  This property, of type Unsigned, is the maximum number of 
octets that may be contained in a single, indivisible applica-
tion layer protocol data unit. The value of this property shall 
be greater than or equal to 50. The value of this property is 
also subject to the limitations of the data link technology 
used. 
6.42 Max_Pres_Value 
Data Type  REAL 
Objects    Analog input, Analog output 
Description  This property, of type REAL, indicates the highest number 
in engineering units that can be reliably obtained for the 
Present_Value property of this object. 
6.43 Max_Segments_Accepted 
Data Type  Unsigned 
Objects  Device 
Description  The Max_Segments_Accepted property, of type Unsigned, 
shall indicate the maximum number of segments of an 
APDU that this device will accept. 
6.44 Min_Pres_Value 
Data Type  REAL 
Objects    Analog input, Analog output 
Description  This property, of type REAL, indicates the lowest number in 
engineering units that can be reliably obtained for the Pre-
sent_Value property of this object. 