Technical data
    List of all BACnet Properties in Native Operation   • 297 
  Object_Type 
WAGO-I/O-SYSTEM 750   
BACnet/IP Controller 
6.55 Object_Type 
Data Type  BACnetObjectType 
Objects  Device, Calendar, File, Binary input, Binary output, Analog 
input, Analog output, Scheduler 
Description  This property, of the type BACnetObjectType, indicates 
membership in a particular object type class. The value of 
this property for native objects can be DEVICE, 
CALENDAR, FILE, BINARY_INPUT, 
BINARY_OUTPUT, ANALOG_INPUT, 
ANALOG_OUTPUT or SCHEDULE. 
6.56 Out_Of_Service 
Data Type BOOLEAN 
Objects  Binary input, Binary output, Analog input, Analog output, 
Scheduler 
Description  Binary Input/Analog Input/Binary Out-
put/Analog Output: 
The Out_Of_Service property, of the type BOOLEAN, indi-
cates whether the physical input or output that the object 
represents is active (TRUE) or not (FALSE). If the value of 
Out_Of_Service is TRUE, the property Present_Value is not 
coupled with the physical input or output and changes are 
not carried out here. In addition, the Reliability property and 
the corresponding state of the FAULT flag of the 
Status_Flags property are decoupled from the physical input 
or output when Out_Of_Service is TRUE. While the 
Out_Of_Service property is TRUE, the Present_Value and 
Reliability properties may be changed to any value as a 
means of simulating specific fixed conditions or for testing 
purposes. Other functions that depend on the state of the 
Present_Value or Reliability properties must react to 
changes in value while Out_Of_Service is TRUE, as if those 
changes had occurred in the physical input or output. For the 
Output Objects, the property Present_Value can still be con-
trolled via the BACnet Command Prioritization Mechanism 
if Out_Of_Service is TRUE. 