Technical data
300 •  List of all BACnet Properties in Native Operation 
 Present_Value 
 WAGO-I/O-SYSTEM 750 
BACnet/IP Controller 
Binary Output: 
For this object, the property of the type BACnetBinaryPV 
indicates the logical state of the Binary Output. The logical 
state of the output is either INACTIVE or ACTIVE. The re-
lationship between the Present_Value and the physical state 
of the output is determined by the Polarity property. Possi-
ble states are summarized in Tab. 6-9. 
   Tab. 6-9: Interrelationships for BACnet Polarity (Binary Output) 
Present_Value  Polarity  Physical state of 
the output 
Physical state of 
device 
INACTIVE  NORMAL  OFF or INACTIVE  Not in operation 
ACTIVE NORMAL ON or ACTIVE In operation 
INACTIVE  REVERSE  ON or ACTIVE  Not in operation 
ACTIVE  REVERSE  OFF or INACTIVE  In operation 
Analog Input: 
This property, of the type REAL, indicates the current value, 
in engineering units, of the input being measured. The Pre-
sent_Value property must be writable when Out_Of_Service 
is TRUE. 
Analog output: 
This property, of type REAL, indicates the current value, in 
engineering units, of the output. 
Schedule: 
This property indicates the current value of the schedule. 
This can be any primitive data type. As a result, most ana-
log, binary, and enumerated values may be used. This prop-
erty must be writable when Out_Of_Service is TRUE (see 
section 6.56, "Out_of_Service"). 
Any change in the value of this property shall be written to 
all members of the List_Of_Object_Property_References 
property. An error writing to any member of the list shall 
not stop the Schedule object from writing to the remaining 
members. 










