Technical data
    List of all BACnet Properties in Native Operation   • 303 
  Protocol_Revision 
WAGO-I/O-SYSTEM 750   
BACnet/IP Controller 
6.62 Protocol_Revision 
Data Type  Unsigned 
Objects  Device 
Description  This property, of the type Unsigned, indicates the minor re-
vision level of the BACnet standard. This value starts at 1 
and increases in increments for any substantive change(s) to 
the BACnet standard that affect device communication or 
behavior. This value reverts to zero upon each change to the 
Protocol_Version property. Changes to the values for Proto-
col_Version and Protocol_Revision are recorded in the His-
tory of Revisions at the end of this standard. 
This property is required for all devices implementing 
BACnet Protocol_Version 1, Protocol_Revision 1 and 
above. Absence of this property indicates a device imple-
mented to a version of the standard prior to the definition of 
the Protocol_Revision property. 
6.63 Protocol_Services_Supported 
Data Type BACnetServicesSupported 
Objects  Device 
Description  This property, of the type BACnetServicesSupported, indi-
cates which standardized protocol services are supported by 
this device's protocol implementation. 
6.64 Protocol_Version 
Data Type  Unsigned 
Objects  Device 
Description  This property, of type Unsigned, represents the version of 
the BACnet protocol supported by this BACnet Device. 
Every major revision of BACnet increases this version num-
ber by one. The initial release of BACnet is Version 1. 