Technical data
    List of all BACnet Properties in Native Operation   • 305 
  Relinquish_Default 
WAGO-I/O-SYSTEM 750   
BACnet/IP Controller 
 Binary Input: 
{NO_FAULT_DETECTED, NO_SENSOR, OPEN_LOOP, 
SHORTED_LOOP, UNRELIABLE_OTHER} 
Binary Output: 
{NO_FAULT_DETECTED, NO_OUTPUT, OPEN_LOOP, 
SHORTED_LOOP, UNRELIABLE_OTHER} 
Analog Input: 
{NO_FAULT_DETECTED, NO_SENSOR, 
OVER_RANGE, UNDER_RANGE, OPEN_LOOP, 
SHORTED_LOOP, UNRELIABLE_OTHER} 
Analog Output: 
{NO_FAULT_DETECTED, OPEN_LOOP, 
SHORTED_LOOP, NO_OUTPUT, 
UNRELIABLE_OTHER} 
 Schedule: 
The property Reliability indicates whether the properties of 
the schedule object are constant. All non-ZERO values used 
in the Weekly_Schedule, the Exception_Schedule, and the 
Schedule_Default properties shall be of the same data type, 
and all members of the 
List_Of_Object_Property_References shall be writable with 
that data type. If these conditions are not met, then this 
property shall have the value CONFIGURATION_ERROR. 
The Reliability property for this object may have any of the 
following values: 
{NO_FAULT_DETECTED, CONFIGURATION_ERROR, 
UNRELIABLE_OTHER} 
If the List_Of_Object_Property_References contains a 
member that references a property in a remote device, the 
detection of a configuration error may be delayed until an 
attempt is made to write a scheduled value. 
6.68 Relinquish_Default 
Data Type  see Objects 
Objects     Binary Output (BACnetBinaryPV), Analog Output (REAL) 
Description  This property is the default value to be used for the Pre-
sent_Value property when all command priority values in 
the Priority_Array property have a ZERO value. 