Technical data
    List of all BACnet Properties in Native Operation   • 307 
  Status_Flags 
WAGO-I/O-SYSTEM 750   
BACnet/IP Controller 
6.72 Status_Flags 
Data Type  BACnetStatusFlags 
Objects  Binary input, Binary output, Analog input, Analog output, 
Scheduler 
Description  This property, of type BACnetStatusFlags, represents four 
Boolean flags that indicate the general "health" of a binary 
or analog input or output or a scheduler object. Three of the 
flags (for the schedule object two objects) are associated 
with the values of other properties of this object. A more de-
tailed status could be determined by reading the properties 
that are linked to these flags. The relationship between indi-
vidual flags is not defined by the protocol. 
{IN_ALARM, FAULT, OVERRIDDEN, 
OUT_OF_SERVICE} 
IN_ALARM has the following meaning: 
•  Binary Input/Output/Analog Input/Output: 
logical FALSE (0) of the property Event_State has the 
value NORMAL, otherwise logical TRUE (1). 
•  Schedule: 
The value of this flag is logical FALSE (0). 
FAULT has the following meaning: 
Logical TRUE (1) if the Reliability property is present and 
does not have a value of NO_FAULT_DETECTED, other-
wise logical FALSE (0). 
OVERRIDDEN has the following meaning: 
•  Binary Input/Analog Input: 
Logical TRUE (1) if the point has been overridden by 
some mechanism local to the BACnet Device. In this 
case, "overridden" is taken to mean that the Pre-
sent_Value and Reliability properties are no longer 
tracking changes to the physical input. Otherwise, the 
value is logical FALSE (0). 
•  Binary Output/Analog Output: 
Logical TRUE (1) if the point has been overridden by 
some mechanism local to the BACnet Device. In this 
case, "overridden" is taken to mean that the properties 
Present_Value and Reliability no longer represent the 
physical output. Otherwise, the value is logical FALSE 
(0). 