Technical data
308 •  List of all BACnet Properties in Native Operation 
 System_Status 
 WAGO-I/O-SYSTEM 750 
BACnet/IP Controller 
•  Schedule: 
Logical TRUE (1) if the schedule object has been over-
ridden by some mechanism local to the BACnet Device. 
In this case, "overridden" is taken to mean that the Pre-
sent_Value property cannot be changed through BACnet 
services. Otherwise, the value is logical FALSE (0). 
OUT_OF_SERVICE has the following meaning:   
Logical TRUE (1) if the Out_Of_Service property has a 
value of TRUE, otherwise logical FALSE (0). 
6.73 System_Status 
Data Type  BACnetDeviceStatus 
Objects  Device 
Description  This property, of the type BACnetDeviceStatus, reflects the 
current physical and logical state of the BACnet device. 
This property can take on the following values: 
{OPERATIONAL, OPERATIONAL_READ_ONLY, 
DOWNLOAD_REQUIRED, 
DOWNLOAD_IN_PROGRESS, NON_OPERATIONAL} 
6.74 Time_Delay 
Data Type  Unsigned 
Objects    Binary Input, Binary Output, Analog Input, Analog Output 
Description Binary Input:  
This property, of the type Unsigned, specifies the minimum 
period of time in seconds during which the Present_Value 
must remain equal to the Alarm_Value property before a 
TO-OFFNORMAL event is generated, or remain not equal 
to the Alarm_Value property before a TO-NORMAL event 
is generated. 
 Binary Output: 
This property, of the type Unsigned, specifies the minimum 
period of time in seconds during which the Present_Value 
must be different from the Feedback_Value property before 
a TO-OFFNORMAL event is generated or must remain 
equal to the Feedback_Value property before a TO-
NORMAL event is generated. 