Technical data
310 •  List of all BACnet Properties in Native Operation 
 Update_Interval 
 WAGO-I/O-SYSTEM 750 
BACnet/IP Controller 
6.78 Update_Interval 
Data Type  Unsigned 
Objects  Analog Input 
Description  This property, of the type Unsigned, indicates the maximum 
period of time between updates to the Present_Value in 
hundredths of a second when the input is not overridden and 
not out-of-service. 
6.79 UTC_Offset 
Data Type  INTEGER 
Objects  Device 
Description  The UTC_Offset property, of the type INTEGER, indicates 
the number of minutes (-780 to +780) offset between local 
standard time and Universal Time Coordinated. The time 
zones to the west of the zero degree meridian are positive 
values, and those to the east are negative values. The value 
of the UTC_Offset property is subtracted from the UTC re-
ceived in UTCTimeSynchronization service requests to cal-
culate the correct local standard time. 
6.80 Vendor_Identifier 
Data Type  Unsigned16 
Objects  Device 
Description  This property, of the type Unsigned16, is a unique vendor 
identification code, assigned by ASHRAE, which is used to 
distinguish proprietary extensions to the protocol. 