Technical data
    Use in Hazardous Environments  • 329 
  Installation Regulations 
WAGO-I/O-SYSTEM 750   
BACnet/IP Controller 
9.6.2  TÜV Nord Ex-i applications 
For operation in zone 2, the WAGO-I/O-System 750-*** must be mounted in 
an enclosure that fulfills the requirements of the directive 94/9/EG and the 
relevant standards EN 60079-0 and EN 60079-15. The fulfillment of these 
requirements must be certified by an appointed office. 
Only devices that are suitable for operation in areas subject to explosion of 
zone 2 and 22 and that are suitable for the conditions in the place of 
installation (declaration of conformity or certificate from a test office) may be 
connected to not intrinsically safe circuits in zone 2 or zone 22. 
If the interface circuits are operated without the 750-3 fieldbus coupler ../....-... 
(DEMKO 08 ATEX 142851 X), then measures must be taken outside of the 
device so that the rated voltage will not be exceeded by more than 40 % due to 
temporary faults. 
The connection and interruption of non intrinsically-safe circuits under 
voltage is only permissible during installation, maintenance or for repair 
purposes. The simultaneous occurrence of explosive atmosphere and 
installation, maintenance, etc. must be ruled out. 
For operation in zone 22, the WAGO-I/O-System 750-*** must be mounted 
in an enclosure that fulfills the requirements of the directive 94/9/EG and the 
relevant standards EN 61241-0 and EN 61241-1. The fulfillment of these 
requirements must be certified by an appointed office. The housing must be 
marked on the outside with 
II 3 (1) GD Ex nA tD [ia] [iaD] IIC/IIB A22 IP6X T135°C (T4) and/ or 
II 3 (2) GD Ex nA tD [ib] [ibD] IIC/IIB A22 IP6X T135°C (T4). 
The marking must take into account all devices built into the enclosure. 
The manufacturer of the whole device must ensure that taking into account the 
maximum ambient temperature range, the temperature in the enclosure will 
not drop below 0 °C or exceed 55 °C. 
DIP switches, coding switches, and potentiometers that are connected to the 
module may only be operated if an explosive atmosphere can be ruled out. 