2.8 Grounding 
2.8.1  Grounding the DIN Rail 
2.8.1.1 Framework Assembly 
When setting up the framework, the carrier rail must be screwed together with 
the electrically conducting cabinet or housing frame. The framework or the 
housing must be grounded. The electronic connection is established via the 
screw. Thus, the carrier rail is grounded. 
Attention 
Care must be taken to ensure the flawless electrical connection between the 
carrier rail and the frame or housing in order to guarantee sufficient ground-
ing. 
2.8.1.2 Insulated Assembly 
Insulated assembly has been achieved when there is constructively no direct 
conduction connection between the cabinet frame or machine parts and the 
carrier rail. Here the earth must be set up via an electrical conductor. 
The connected grounding conductor should have a cross section of at least 
4 mm
2
. 
Recommendation 
The optimal insulated setup is a metallic assembly plate with grounding con-
nection with an electrical conductive link with the carrier rail. 
The separate grounding of the carrier rail can be easily set up with the aid of 
the WAGO ground wire terminals. 
Item No.  Description 
283-609  1-conductor ground (earth) terminal block make an automatic contact to 
the carrier rail; conductor cross section: 0.2 -16 mm
2
Note: Also order the end and intermediate plate (283-320). 